Product Overview
LES 15-NP is a LES series current transducer. For the electronic measurement of current: DC, AC, pulsed with galvanic separation between the primary and the secondary circuit. Applications includes AC variable speed drives, static converters for DC motor drives, battery supplied applications, UPS, SMPS, power supplies for welding applications and solar inverter.
- Closed loop multi-range current transducer, voltage output
- Unipolar supply voltage, compact design for PCB mounting
- Very low offset drift, very good dv/dt immunity, CAS footprint compatible
- RMS voltage for AC insulation test is 4.3KV
- V0 case material (according to UL 94)
- Supply voltage range from 4.75 to 5.25V (TA = 25°C, UC = +5V, NP = 1 turn, RL = 10kohm)
- Primary nominal RMS current is 6A typ (TA = 25°C, UC = +5V, NP = 1 turn, RL = 10kohm)
- Output voltage range from 0.25 to 4.75V (UC = +5V, TA = 25°C, UC = +5V, NP = 1 turn, RL = 10kohm)
- Frequency bandwidth (±1dB) is 300KHz min (RL = 1kohm, TA = 25°C)
- Ambient operating temperature range from -40 to 105°C
Warnings
Market demand for this product has caused an extension in leadtimes. Delivery dates may fluctuate. Product exempt from discounts.
Technical Specifications
Voltage
4.75V to 5.25V
AC / DC / Pulsed
-51A to 51A
Closed Loop Hall Effect
0.4µs
Voltage
-40°C
LES Series
4.75V
5.25V
0.45%
-51A to 51A
15A
0.45%
Through Hole
105°C
No SVHC (27-Jun-2024)